1 Scope
This part of the IEC 60255 series describes the product safety requirements for measuring relays and protection
equipment having a rated a.c. voltage up to 1 000 V with a rated frequency up to 65 Hz,
or a rated d.c. voltage up to 1 500 V. Above these limits, IEC 60664‑1 is applicable for the determination of clearance , creepage distance and withstand test voltage.
This standard details essential safety requirements to minimize the risk of fire and
hazards caused by electric shock or injury to the user .
This standard does not cover the safety requirements of installations. It does cover
all the ways in which the equipment may be mounted and used in cubicles, racks and
panels, and also retesting. This standard also applies to auxiliary devices such as
shunts, series resistors, transformers, etc., that are used in conjunction with measuring
relays and protection equipment and are tested together.
Ancillary equipment used in conjunction with measuring relays and protection equipment
may need to comply with additional safety requirements.
This standard is intended to describe only product safety requirements; therefore,
functional performance of the equipment is not covered.
Functional safety requirements, including EMC functional safety, are not covered by
this standard. Functional safety risk analysis is not within the scope of this product
safety standard.
This standard does not specify the implementation of individual equipment, circuits
and components.