IEC 62439-4:2010
Industrial communication networks - High availability automation networks - Part 4: Cross-network Redundancy Protocol (CRP)
Industrial communication networks - High availability automation networks - Part 4: Cross-network Redundancy Protocol (CRP)
- Статус документа:
- Действующий
- Формат:
- Электронный (PDF)
- Количество страниц:
- 41
- Дата публикации:
- 26 февраля 2010 г.
- Издание:
- IEC IS 62439 edition 1 version 1
- ICS:
- 25.040.40
IEC 62439-4:2010 is applicable to high-availability automation networks based on the ISO/IEC 8802-3 (IEEE 802.3) (Ethernet) technology. It specifies a redundancy protocol that is based on the duplication of the network, the redundancy protocol being executed within the end nodes, as opposed to a redundancy protocol built in the switches. The switchover decision is taken in each node individually. The cross-network connection capability enables single attached end nodes to be connected on either of the two networks. It cancels and replaces IEC 62439 published in 2008 and constitutes a technical revision. It includes the following significant technical changes with respect to IEC 62439 (2008): - adding a calculation method for RSTP (rapid spanning tree protocol, IEEE 802.1Q), - adding two new redundancy protocols: HSR (High-availability Seamless Redundancy) and DRP (Distributed Redundancy Protocol), - moving former Clauses 1 to 4 (introduction, definitions, general aspects) and the Annexes (taxonomy, availability calculation) to IEC 62439-1, which serves now as a base for the other documents, - moving Clause 5 (MRP) to IEC 62439-2 with minor editorial changes, - moving Clause 6 (PRP) was to IEC 62439-3 with minor editorial changes, - moving Clause 7 (CRP) was to IEC 62439-4 with minor editorial changes, and - moving Clause 8 (BRP) was to IEC 62439-5 with minor editorial changes, - adding a method to calculate the maximum recovery time of RSTP in a restricted configuration (ring) to IEC 62439-1 as Clause 8, - adding specifications of the HSR (High-availability Seamless Redundancy) protocol, which shares the principles of PRP to IEC 62439-3 as Clause 5, and - introducing the DRP protocol as IEC 62439-6. This publication is to be read in conjunction with IEC 62439-1:2010.
Abstract
Overview
IEC 62439-4:2010 - Industrial communication networks - High availability automation networks - Part 4: Cross-network Redundancy Protocol (CRP) - defines a redundancy protocol for Ethernet (ISO/IEC 8802-3 / IEEE 802.3) based automation networks. CRP implements redundancy by duplicating networks and running the redundancy logic in the end nodes rather than in switches. Each node makes its own switchover decision and singly attached devices can connect to either of the two networks (cross-network capability). IEC 62439-4 is part of the IEC 62439 high‑availability family and is intended to be read together with IEC 62439-1 (general concepts and calculation methods).
Key topics and technical requirements
- Scope: High-availability automation networks using Ethernet; node-based redundancy (end-node protocol).
- Topology support: Single and double LAN topologies; support for doubly-attached nodes (DANCs) and singly-attached nodes.
- Protocol elements:
- DiagnosticFrame and AnnunciationFrame messaging for status and fault detection.
- Network_Status_Table to track link and node status across networks.
- Multicast and unicast handling, path selection and reception adapter selection rules.
- Redundancy statistics, services and a Management Information Base (MIB).
- Availability and recovery:
- Methods for calculating CRP recovery time and maximum repair time in network configurations.
- Failure detection mechanisms based on diagnostic message arrival and redundancy information exchange.
- Integration: Node configuration and repair procedures; LRE (LAN Redundancy Entity) attributes and their operational impact.
- Standards evolution: This edition replaces IEC 62439 (2008) and aligns with additions across the series (e.g., RSTP calculation, HSR, DRP).
Practical applications and users
- Where used: Industrial automation, process control, manufacturing systems, power substations, critical infrastructure where deterministic, low-latency network recovery is required.
- Who uses it:
- Network architects and automation engineers designing redundant Ethernet topologies.
- Device and equipment manufacturers implementing node-based redundancy features.
- System integrators and consultants specifying high-availability solutions.
- Test labs and certification bodies verifying compliance and recovery performance.
- Benefits: Maintains standard Ethernet compatibility while providing deterministic failover, supports single-attached endpoints via cross-network connectivity, and enables distributed failure decisions at nodes.
Related standards
- IEC 62439-1:2010 - General concepts and calculation methods (mandatory companion).
- IEC 62439-2 - MRP (Media Redundancy Protocol).
- IEC 62439-3 - PRP (Parallel Redundancy Protocol) and HSR (High-availability Seamless Redundancy).
- IEC 62439-5 - BRP (Bridge Redundancy Protocol).
- IEC 62439-6 - DRP (Distributed Redundancy Protocol).
Keywords: IEC 62439-4, Cross-network Redundancy Protocol, CRP, high availability, industrial communication networks, Ethernet redundancy, PRP, HSR, DRP, recovery time, RSTP.
Технические детали
- Технический комитет
- SC 65C - Industrial networks
- SKU
- IEC 62439-4:2010
Похожие стандарты
Стандарты, упомянутые в описании
IEC 62439-2:2016
ДействующийIndustrial communication networks - High availability automation networks - Part 2: Media Redundancy Protocol…
Overview IEC 62439-2:2016 is an international standard developed by the International Electrotechnical Commission (IEC) that addresses high-availability automation networks built on ISO/IEC/IEEE 8802…
IEC 62439-3:2016
ДействующийIndustrial communication networks - High availability automation networks - Part 3: Parallel Redundancy Proto…
Overview IEC 62439-3:2016 - Industrial communication networks - High availability automation networks - Part 3: Parallel Redundancy Protocol (PRP) and High-availability Seamless Redundancy (HSR) - de…
IEC 62439-5:2016
ОтменёнIndustrial communication networks - High availability automation networks - Part 5: Beacon Redundancy Protoco…
IEC 62439-6:2010
ДействующийIndustrial communication networks - High availability automation networks - Part 6: Distributed Redundancy Pr…
Overview IEC 62439-6:2010 - Industrial communication networks - High availability automation networks - Part 6: Distributed Redundancy Protocol (DRP) - defines a deterministic recovery protocol for E…