ISO 10294-5:2005
Fire resistance tests — Fire dampers for air distribution systems — Part 5: Intumescent fire dampers
Fire resistance tests — Fire dampers for air distribution systems — Part 5: Intumescent fire dampers
- Статус документа:
- Отменён
- Формат:
- Электронный (PDF)
- Количество страниц:
- 24
- Дата публикации:
- 16 марта 2005 г.
- Издание:
- ISO IS 10294 edition 1 version 1
- ICS:
- 13.220.50
ISO 10294-5:2005 describes the test requirements related to intumescent fire dampers. It identifies the minor modifications needed to adapt the test method described in ISO 10294-1 (which was intended for mechanical dampers) to suit intumescent fire dampers. Additional tests are included to give an assessment of the operational reliability of intumescent fire dampers. This test is intended for intumescent fire dampers that will be classified as EI dampers in accordance with ISO 10294-2. Without the addition of a mechanical damper, they are unable to achieve the "S" classification, which includes a leakage limit imposed at ambient temperatures.
Abstract
Overview
ISO 10294-5:2005 specifies fire resistance test requirements for intumescent fire dampers used in ducted air distribution systems. It describes the modifications needed to apply the general damper test method (ISO 10294-1) to non‑mechanical, heat‑activated intumescent devices and adds material and operational tests to assess reliability. The standard is intended for dampers to be classified as EI dampers under ISO 10294-2 (note: intumescent-only dampers cannot achieve the “S” leakage classification without an added mechanical damper).
Key topics and requirements
- Scope and purpose
- Adapts ISO 10294-1 test procedures for intumescent behavior and defines additional material tests.
- Targets classification as EI dampers per ISO 10294-2.
- Test procedure modifications
- Opening/closing cycles: the 50-cycle mechanical damper test is not applicable (intumescence is irreversible).
- Time to close: no requirement to close before 2 minutes; leakage performance must be met after 5 minutes (furnace stabilization).
- Condensing device: required before the flow-measuring device; gas temperature at the flow meter must not exceed 40 °C (example solution: water tank with ~9 m of measuring duct immersed).
- Material and reliability tests
- Thermal activation temperature test: oven range 25 °C–350 °C (±3 °C); begin 30 °C below manufacturer activation temperature, increase in 5 °C steps until activation occurs.
- Faulty set-off (conditioning) test: specimens held at chosen operating temperature (standard 60 °C) for 60 minutes; thickness measured before/after - variation must not exceed 5%.
- Expansion pressure tests: methods include disc pressure, pipe pressure, and die‑set pressure (appropriate method depends on whether material is covered/skinned or processed).
- Specimen sampling and conditioning: initial type testing typically uses 10 specimens; factory control often uses 2; condition samples at 23 °C ±4 °C and 50% RH for at least 7 days.
- Reporting and annexes
- Test report requirements plus normative Annex A (durability) and informative Annexes B and C (test apparatus and application guidance).
Applications and users
- Manufacturers of intumescent fire dampers - for type testing and production control
- Independent test laboratories and certification bodies - to perform standardized fire resistance testing
- Fire safety engineers, HVAC designers, installers, and building authorities - to evaluate product suitability for ducted systems and ensure compliance with EI classification requirements
- Specifiers and procurement teams - to reference standardized test methods in technical specifications
Related standards
- ISO 10294-1:1996 (Test method)
- ISO 10294-2:1999 (Classification and criteria)
- ISO 10294-3:1999 (Guidance)
- ISO 10294-4:2001 (Thermal release mechanism)
- ISO 13943 (Fire safety - Vocabulary)
Keywords: ISO 10294-5:2005, intumescent fire dampers, fire resistance tests, EI classification, expansion pressure test, thermal activation temperature, faulty set-off, fire dampers for air distribution systems.