ISO 16358-2:2013
Air-cooled air conditioners and air-to-air heat pumps — Testing and calculating methods for seasonal performance factors — Part 2: Heating seasonal performance factor
Air-cooled air conditioners and air-to-air heat pumps — Testing and calculating methods for seasonal performance factors — Part 2: Heating seasonal performance factor
- Статус документа:
- Действующий
- Формат:
- Электронный (PDF)
- Количество страниц:
- 38
- Дата публикации:
- 9 апреля 2013 г.
- Издание:
- ISO IS 16358 edition 1 version 1
- ICS:
- 23.120
ISO 16358-2:2013 specifies the testing and calculating methods for seasonal performance factor of equipment covered by ISO 5151, ISO 13253 and ISO 15042. For the purposes of ISO 16358-2:2013, it is assumed that any make-up heating will be provided by electric heaters running concurrently with the heat pump. ISO 16358-2:2013 also specifies the seasonal performance test conditions and the corresponding test procedures for determining the seasonal performance factor of equipment, as specified above, under mandatory test conditions and is intended for use only in marking, comparison, and certification purposes. ISO 16358-2:2013 does not apply to the testing and rating of: water-source heat pumps or water-cooled air conditioners; portable units having a condenser exhaust duct; individual assemblies not constituting a complete refrigeration system; or equipment using the absorption refrigeration cycle.
Abstract
Overview
ISO 16358-2:2013 - "Air-cooled air conditioners and air-to-air heat pumps - Testing and calculating methods for seasonal performance factors - Part 2: Heating seasonal performance factor" specifies standardized methods to test and calculate the Heating Seasonal Performance Factor (HSPF) for air-cooled and air-to-air heat pumps covered by ISO 5151, ISO 13253 and ISO 15042. The standard defines test conditions, test procedures and calculation rules for seasonal heating performance used for marking, comparison and certification. It assumes any make‑up heating is provided by electric heaters running concurrently with the heat pump.
Key technical topics and requirements
- Scope and exclusions: Applies to air-cooled and air-to-air heat pumps covered by ISO 5151/13253/15042. Does NOT apply to water‑source or water‑cooled units, portable units with condenser exhaust ducts, individual assemblies (not complete systems), or absorption-cycle equipment.
- Definitions & metrics: Formal definitions for HSPF, Total HSPF (THSPF), Heating Seasonal Total Load (HSTL), Heating Seasonal Energy Consumption (HSEC), Part Load Factor (PLF) and degradation coefficient (CD).
- Test conditions and procedures: Mandatory seasonal test conditions, binning by outdoor temperature, and procedures to measure continuous and cyclic operation performance.
- Capacity classifications: Methods cover fixed‑capacity, two‑stage, multi‑stage and variable‑capacity units, with specific approaches for full, half, extended and minimum capacity operations.
- Calculations: Clear calculation methodology for HSPF and THSPF, including how to account for make‑up electric heating, temperature bin distributions, part‑load behavior and cyclic degradation. Normative annexes (e.g., Annex C) define testing for degradation coefficients; informative annexes provide figures and calculation examples.
Practical applications - who uses this standard
- Manufacturers and product designers: to report compliant HSPF values and design for seasonal efficiency targets.
- Independent test laboratories: to run repeatable, standardized seasonal performance tests for certification and comparison.
- Regulators and certifiers: to set energy labeling, minimum efficiency standards and compliance protocols.
- HVAC specifiers, consultants and building designers: to compare systems based on seasonal heating performance for climate‑specific selections.
- Energy program administrators: for incentive schemes that require standardized efficiency metrics.
Related standards
- ISO 5151 - Non‑ducted air conditioners and heat pumps: testing and rating
- ISO 13253 - Ducted air conditioners and air‑to‑air heat pumps: testing and rating
- ISO 15042 - Multiple split‑system air‑conditioners and air‑to‑air heat pumps: testing and rating
- ISO 16358-1 & -3 - Cooling seasonal performance factor and Annual performance factor (other parts of the series)
Keywords: ISO 16358-2:2013, HSPF, heating seasonal performance factor, air-cooled air conditioners, air-to-air heat pumps, seasonal performance testing, ISO 5151, PLF, THSPF.
Технические детали
- Технический комитет
- ISO/TC 86/SC 6 - Testing and rating of air-conditioners and heat pumps
- SKU
- ISO 16358-2:2013
Похожие стандарты
Стандарты, упомянутые в описании
ISO 5151:2017
ДействующийNon-ducted air conditioners and heat pumps — Testing and rating for performance
Overview ISO 5151:2017 - Non-ducted air conditioners and heat pumps - Testing and rating for performance defines standard test conditions and methods to determine capacity and efficiency ratings for…
ISO 13253:2017
ДействующийDucted air-conditioners and air-to-air heat pumps — Testing and rating for performance
Overview ISO 13253:2017 - "Ducted air-conditioners and air-to-air heat pumps - Testing and rating for performance" defines standardized performance testing and rating procedures for ducted, air-coole…
ISO 15042:2017
ДействующийMultiple split-system air conditioners and air-to-air heat pumps — Testing and rating for performance
Overview ISO 15042:2017 - Multiple split-system air conditioners and air-to-air heat pumps - provides standardized procedures for testing and rating capacity and efficiency of air-cooled multi‑split…
ISO 16358-1:2013
ДействующийAir-cooled air conditioners and air-to-air heat pumps — Testing and calculating methods for seasonal performa…
Overview ISO 16358-1:2013 - "Air-cooled air conditioners and air-to-air heat pumps - Testing and calculating methods for seasonal performance factors - Part 1: Cooling seasonal performance factor" -…