ISO 18566-4:2017
Building environment design — Design, test methods and control of hydronic radiant heating and cooling panel systems — Part 4: Control of ceiling mounted radiant heating and cooling panels
Building environment design — Design, test methods and control of hydronic radiant heating and cooling panel systems — Part 4: Control of ceiling mounted radiant heating and cooling panels
- Статус документа:
- Действующий
- Формат:
- Электронный (PDF)
- Количество страниц:
- 8
- Дата публикации:
- 13 июля 2017 г.
- Издание:
- ISO IS 18566 edition 1 version 1
- ICS:
- 91.040.01
ISO 18566-4:2017 specifies the control of ceiling mounted radiant heating and cooling panels. The requirements in this document are applicable only to the components of the heating/cooling systems and the elements which are part of the heating/cooling panels and which are installed to provide heating and/or cooling. ISO 18566-4:2017 is applicable to water-based ceiling mounted radiant heating and cooling panels in residential, commercial and industrial buildings. The methods apply to systems mounted under the ceiling with or without open air gaps between the panels and the ceiling.
Abstract
Overview
ISO 18566-4:2017 - “Building environment design - Design, test methods and control of hydronic radiant heating and cooling panel systems - Part 4” - specifies control requirements for ceiling mounted water‑based radiant heating and cooling panels. It applies to systems installed under ceilings (with or without open air gaps) in residential, commercial and industrial buildings and covers only the components and elements that form part of the panel heating/cooling assemblies. Embedded panels (integrated into ceilings, walls or floors) are not covered.
Key topics and technical requirements
- Control system capabilities: Controls must vary heating/cooling outputs and maintain predetermined room or panel surface temperatures to meet design conditions under changing internal loads and outdoor climate.
- Design documentation: Control strategies and specifications must be included in design documents to ensure installed systems perform as simulated.
- Control hierarchy: Defines three control levels - central, zone, and local (space) control - and performance classifications (manual, automatic, timing, advanced timing).
- Central control: Typically manages supply/mean water temperature (via mixing valves or plant set points) based on outside temperature or representative zone conditions. For cooling, central control should consider the highest zone dew point to prevent condensation.
- Zone control: Groups spaces with similar thermal needs (e.g., north/south orientation) to optimize energy use and water temperature requirements.
- Local (space) control: Room-level sensors and valve/flow control allow occupant set‑point adjustments; wireless links are noted as useful where wiring limits sensor placement.
- Sensors and monitoring: Room temperature, humidity (for dew point), supply/return/panel surface temperature sensors and outside temperature sensors are recommended inputs to controls and building management systems (BMS).
- Condensation prevention: Systems must include control strategies to avoid surface condensation - e.g., minimum supply water temperature limits tied to measured dew point or surface temperature feedback (see Annex A).
- Flow control, thermal mass and dynamics: Control design must account for panel thermal mass, time constants, self‑regulating effects and distribution losses to avoid simultaneous heating and cooling and to optimize energy efficiency.
- Protection functions: Controls should provide frost/moisture protection when comfort temperatures are not required.
Applications
- Specifying control schemes for ceiling-mounted hydronic radiant heating and cooling installations
- Integrating radiant panel systems into BMS and HVAC plant control
- Designing zoning strategies and condensation‑prevention controls in offices, apartments, hospitals, schools and industrial spaces
- Informing manufacturer and installer requirements for valves, sensors and control units
Who uses this standard
- HVAC and building services engineers
- Controls and BMS integrators
- Radiant panel manufacturers
- Building designers, energy consultants and facility managers
- Installers and commissioning teams
Related standards
- ISO 18566-1, ISO 18566-2, ISO 18566-3 (other parts of the series)
- ISO 11855 (embedded radiant systems - related but distinct scope)
Keywords: ISO 18566-4, ceiling mounted radiant panels, hydronic radiant heating and cooling, control, condensation prevention, mixing valve, BMS, water‑based radiant systems.
Технические детали
- Технический комитет
- ISO/TC 205 - Building environment design
- SKU
- ISO 18566-4:2017
Похожие стандарты
Стандарты, упомянутые в описании