IEC/IEEE 80005-1:2019 PDF
Utility connections in port - Part 1: High voltage shore connection (HVSC) systems - General requirements
Utility connections in port - Part 1: High voltage shore connection (HVSC) systems - General requirements
- Статус документа:
- Действующий
- Формат:
- Электронный (PDF)
- Количество страниц:
- 159
- Дата публикации:
- 2 февраля 2022 г.
- Издание:
- IEC IS 80005 edition 2 version 1
- ICS:
- 01
IEC/IEEE 80005-1:2019 describes high-voltage shore connection (HVSC) systems, onboard the ship and on shore, to supply the ship with electrical power from shore. This document is applicable to the design, installation and testing of HVSC systems and addresses: - HV shore distribution systems, - shore-to-ship connection and interface equipment, - transformers/reactors, - semiconductor/rotating frequency convertors, - ship distribution systems, and - control, monitoring, interlocking and power management systems. It does not apply to the electrical power supply during docking periods, for example dry docking and other out of service maintenance and repair. Additional and/or alternative requirements can be imposed by national administrations or the authorities within whose jurisdiction the ship is intended to operate and/or by the owners or authorities responsible for a shore supply or distribution system. It is expected that HVSC systems will have practicable applications for ships requiring 1 MVA or more or ships with HV main supply. Low-voltage shore connection systems are not covered by this document. This second edition cancels and replaces the first edition published in 2012. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: a) modification of 4.1, Figure 1: transformer on ship is optional, earthing switches on ship removed; b) 4.2.2 and new item 11.3: alternative procedure of periodic testing added; c) modification of 4.9: - minimum current value in the safety circuits shall be 50 mA; - opening of safety loop shall cause the automatic opening of ship and shore HVSC circuit breakers in a maximum time of 200 ms; d) modification of 5.2: added Figure on harmonic contents; e) modification of 6.2.3: – earthing transformer with resistor can be used also on the secondary side; – neutral earthing resistor rating in amperes shall be minimum 25 A, 5 s; f) modification of all annexes: the safety circuits shall be mandatory; g) modification of A.2.1: a metallic shield shall be installed at least on the power cores or common on pilot wires; h) modification of B.7.2.1: new safety circuit introduced: single line diagram and description; i) modification of C.4.1: SLD for cruise ships was updated, also the safety circuits to be coherent with main body, IEC symbols and introduced more details about the control socket-outlets and plugs manufacturer type; j) modification of C.7.3.1: - shore power connector pin assignment is updated; - all cruise ships shall use 4 cables in all cases; k) added D.6.1: the supply point on shore can be fixed or movable; l) modification of D.7.3.2: the voltage used in the pilot circuit for container ships shall be less than 60 V DC or 25 V AC. m) added D.8.6 and D.9.3.1: automatic restart and synchronization alternatives; n) Annex E set to informative; o) Annex F set to informative.
Abstract
Overview
IEC/IEEE 80005-1:2019 (consolidated edition 2.1, 2022) is the international standard for High Voltage Shore Connection (HVSC) systems that supply ships with electrical power from shore. It sets general requirements for design, installation, testing and operation of HVSC systems both onboard the ship and on shore. The standard is intended primarily for ships requiring about 1 MVA or more or ships with an HV main supply and does not cover low-voltage shore connections or ship electrical supply during dry docking/out-of-service maintenance.
Key topics and technical requirements
- System scope: HV shore distribution systems, shore-to-ship connection/interface equipment, transformers/reactors, semiconductor and rotating frequency convertors, ship distribution systems, control/monitoring, interlocking and power management systems.
- Safety circuits: Now mandatory across annexes; minimum loop current set to 50 mA and opening the safety loop must trip ship and shore HVSC breakers within 200 ms.
- Transformers & earthing: Shipboard transformer is optional; earthing switches on ship removed in this edition. Neutral earthing resistor rating specified (minimum 25 A, 5 s); earthing transformer with resistor can be used on secondary side.
- Connections & cable systems: Requirements for ship-to-shore cables, pilot contacts, earth contacts, metallic shielding on power cores or common on pilot wires, connector pin assignments (updated), cable management, monitoring of cable tension/length, and connector protection.
- Control, synchronization & restart: Provisions for load transfer via blackout, automatic synchronization alternatives, and automatic restart/synchronization options added.
- Testing & verification: Initial shore- and ship-side tests, first-call tests, periodic maintenance and alternative periodic testing procedures are addressed.
- Ship-type specific annexes: Normative requirements for Ro‑Ro, cruise ships (e.g., cruise ships to use four cables), and container ships (pilot circuit voltage limits:
Технические детали
- Технический комитет
- TC 18 - Electrical installations of ships and of mobile and fixed offshore units
- SKU
- IEC/IEEE 80005-1:2019
Похожие стандарты
Другие стандарты IEC
IEC 60050-161:1990/AMD2:1998
ДействующийAmendment 2 - International Electrotechnical Vocabulary (IEV) - Part 161: Electromagnetic compatibility
IEC 60050-161:1990/AMD2:1998 – Electromagnetic Compatibility Vocabulary Amendment ### Overview The IEC 60050-161:1990/AMD2:1998 is the second amendment to the International Electrotechnical Vocabular…