ISO 21925-1:2018 - Fire resistance tests - Fire dampers for air distribution systems - Part 1: Mechanical dampers - defines a standardized test method to determine how mechanical fire dampers resist heat and prevent the spread of fire and smoke through ducted air distribution systems. The standard applies to mechanical fire dampers (not dampers used only for smoke control, air-transfer-only devices, or dampers in suspended ceilings). It consolidates earlier ISO 10294 parts into a single document and includes safety notes about possible release of toxic gases during testing.
Key topics and technical requirements
- Scope and applicability: Tests mechanical dampers for fire and smoke spread between fire compartments via air ducts; excludes smoke-only systems and suspended-ceiling installations.
- Test principles: Damper installed representative of real practice, test starts with damper in the open position to expose the actuating/thermal release mechanism to furnace conditions; measures integrity, insulation (for insulated dampers), and leakage.
- Leakage measurement: Tightness of the closed damper measured by direct flow at a constant pressure differential (commonly 300 Pa, higher permitted for special applications).
- Apparatus:
- Furnace meeting ISO 834-1 heating and pressure conditions.
- Connecting duct (welded steel, ~1.5 ± 0.1 mm thickness, length = 2× diagonal dimension up to 2 m) with gas-tight observation port.
- Measuring station using orifice, Venturi or equivalent and straightening as per ISO 5167 to determine volumetric flow.
- Exhaust fan system capable of maintaining test underpressure and control within ±5%.
- Test construction & installation: Details on specimen size, installation, supporting construction (walls/floors), separation and mounting options (within openings, mounted on face, remote), conditioning and instrumentation.
- Actuating & thermal release mechanisms: Tests assess the ability of fusible links, memory metals, frangible bulbs or sensors to trigger closure under fire conditions; annexes provide alternative mechanisms and reliability tests.
- Reporting, classification & field of application: Specifies test report contents, classification criteria, number of tests, and direct field application guidance (size limits, mounting conditions, separation considerations).
Practical applications - who uses this standard
- Fire test laboratories and certification bodies for validating damper performance.
- Fire safety engineers and consultants specifying compliant fire dampers in building designs.
- HVAC and ductwork manufacturers to design and test mechanical fire dampers.
- Regulatory authorities and code officials assessing compliance with fire-resistance requirements.
- Facilities managers and specifiers selecting dampers for compartmentation and life-safety systems.
Related standards