Overview
ISO 2620:2024 specifies a standardized method for the sampling and analysis of volatile organic compounds (VOCs) in natural gas and biomethane. The method uses thermal desorption coupled with gas chromatography and flame ionization and/or mass spectrometry detectors (TD‑GC‑FID/MS). It covers VOC families commonly found in biogas and biomethane-such as siloxanes, terpenes, organic sulfur compounds, ketones, alkanes and furans-and supports traceable, fit‑for‑purpose testing for grid injection and transport fuel compliance.
Key topics and technical requirements
- Analytical principle: Adsorb VOCs on sorbent tubes, thermally desorb into a GC with capillary column, identify by MS (EI mode) and/or retention indices, quantify with FID and/or MS.
- Detectors & instrumentation: TD‑GC with capillary column; MS (electron ionization) and/or FID; recommended two‑stage thermal desorption with a cooling trap for focusing.
- Sorbent tubes: Use preconditioned tubes compatible with TD systems (typical ~200 mg sorbent); condition tubes at temperatures below adsorbent limits and 25 °C above intended desorption temp.
- Sampling: Collect accurately known gas volume using calibrated volumetric flow controllers (typical sampling flows 50–500 ml/min; typical sample times 1–4 min). Use short, passive tubing and field tube blanks to assess background contamination.
- Calibration and spiking: Use individual VOC standards of purity >99%. Prepare liquid spiking solutions (examples given at ~0.2, 0.04 and 0.01 mg/ml) and prepare standard tubes by liquid introduction and inert gas purging.
- Performance: Expected quantification limit is around 2–5 ng on tube (equivalent to ~20–50 μg/m3 for a 100 ml sample).
- Documentation & QA: Includes requirements for field blanks, sample records (flow, volume, location, temperature, pressure), and quality assurance procedures.
Applications and users
ISO 2620:2024 is intended for:
- Analytical laboratories performing VOC characterization of biomethane and natural gas
- Biomethane producers and biogas upgrading facilities monitoring residual VOCs
- Gas grid operators and regulators requiring conformity assessment for injection
- Transport fuel suppliers using biomethane as compressed or liquefied gas
- Product testing and R&D teams evaluating siloxanes, terpenes and sulfur compounds in renewable gases
Practical uses include compliance testing, process troubleshooting, impurity profiling before grid injection, and establishing metrological traceability for market trade.