Overview
ISO 3008-1:2025 - Fire resistance tests - Door and shutter assemblies - Part 1: General requirements specifies a standardized method for determining the fire resistance of door and shutter assemblies (including hinged, sliding, folding, rolling, tilting doors, removable wall panels and self-closing openable windows) installed in vertical separating elements. Designed to be used in conjunction with ISO 834-1, this second edition updates general requirements, adds a normative Annex C on fire-seal testing, and clarifies preconditioning and unexposed-surface measurement locations. The standard excludes lift landing doors (covered by ISO 3008-2).
Key topics and technical requirements
ISO 3008-1:2025 sets out technical requirements and test protocols, including:
- Test specimen requirements: size, number, design, construction and verification of door and shutter assemblies.
- Installation and supporting construction: definitions of associated/supporting construction, restraint, gaps and installation details that affect test results.
- Preconditioning: conditioning for moisture and mechanical pre-conditioning (e.g., cycling) prior to fire tests.
- Instrumentation and measurement: placement and use of temperature sensors (furnace and unexposed-face thermocouples), pressure measurement, heat-flux measurement, deflection monitoring and associated apparatus.
- Test procedure: procedures to conduct the fire-resistance test in conjunction with ISO 834-1 fire curves and furnace conditions.
- Performance criteria: pass/fail criteria for integrity and insulation, including how to assess unexposed-face temperatures and maximum temperature limits.
- Test reporting and field of direct application: required test-report content and guidance for direct application of test results to timber, steel and glazed constructions and hardware.
- Normative and informative annexes: Annex A (conditioning requirements for supporting constructions), Annex B (estimating radiant heat flux), and new Annex C (testing of fire seals).
Practical applications - who uses this standard
ISO 3008-1:2025 is essential for:
- Fire test laboratories conducting standardized fire-resistance tests on door and shutter assemblies.
- Door and shutter manufacturers developing products, validating fire performance, and preparing technical documentation for certification.
- Architects, specifiers and façade engineers selecting compliant fire doors and detailing installations that meet performance expectations.
- Regulatory authorities, certification bodies and insurance assessors evaluating compliance with building regulations and fire safety codes.
- Fire safety consultants and researchers modeling fire performance and comparing assemblies.
Related standards and references
- ISO 834-1:2025 - Elements of building construction - General fire-resistance test requirements (used alongside ISO 3008-1)
- ISO 3008-2 - Lift landing doors (exclusion)
- ISO 834-8 - Specific requirements for non-loadbearing vertical separating elements
- ISO 13943 - Fire safety vocabulary
Keywords: ISO 3008-1:2025, fire resistance tests, door and shutter assemblies, fire seals, preconditioning, ISO 834-1, fire performance testing, fire test laboratory.