1 Scope
Shall be according to EN 15502‑2‑1:2022, Clause 1 with the following modifications:
Add at the end of the list, after k), following:
“This document covers gas-fired central heating boilers from the types C 1 up to C (11) and the types B 2 , B 3 and B 5 ”:
l) which are fully premixed appliances equipped with an Adaptive Combustion Control Function ( ACCF ) that are intended to be connected to gas grids where the quality of the distributed gas is likely to vary to a large extent over the lifetime of the appliance including
gas grids for natural gases of the second family where up to 20 mol% H 2 is added to the natural gas (H2NG-Y20).
m) which are fully premixed appliances equipped with a Pneumatic Gas/Air Ratio controller
( PGAR ) that are intended to be connected to gas grids for natural gases of the second family
where up to 20 mol% H 2 is added to the natural gas (H2NG-Y20), where the quality of the distributed gas without adding the hydrogen is not likely to vary to a large extent over the lifetime
of the appliance.
Replace in the list following
“This document does not cover all the requirements for”:
ab) and ak) and al) by:
ab) appliances that are intended to be connected to gas grids where the quality of
the distributed gas is likely to vary to a large extent over the lifetime of the appliance (see Annex AB of EN 15502‑1:2021), exce...