1 Scope
This part of IEC 63222 is intended to provide provisions regarding recognized engineering practices applicable
to assess the user’s characteristics in power quality predicted assessment. It summarizes the best practice in non-linear, unbalanced,
impact and fluctuating loads or generations modelling for power quality disturbance anticipation in public power systems at the planning stage.
This document focuses on frequency-domain modelling for AC power quality analysis in electric power networks, typically in the range up to the 50 th harmonic (2,5 kHz in 50 Hz systems or 3 kHz in 60 Hz systems). Unbalance is analyzed
in three-phase systems and only negative sequence component is considered. The approach
and modelling guidelines provided are valid on the representation of user installations
connected to power systems acting as sources of disturbance. Modelling of the network
elements is out of the scope of the document.
These guidelines will be valuable in the definition of power quality performance specifications for user equipment. They will also assist users when modelling
their installation to assess or demonstrate compliance with the emission limits provided
by the system owner/operator and to investigate and specify mitigation measures.