IEC 60099-8:2017
Surge arresters - Part 8: Metal-oxide surge arresters with external series gap (EGLA) for overhead transmission and distribution lines of a.c. systems above 1 kV
Surge arresters - Part 8: Metal-oxide surge arresters with external series gap (EGLA) for overhead transmission and distribution lines of a.c. systems above 1 kV
- Статус документа:
- Действующий
- Формат:
- Электронный (PDF)
- Количество страниц:
- 67
- Дата публикации:
- 14 ноября 2017 г.
- Издание:
- IEC IS 60099 edition 2 version 1
- ICS:
- 29.240.10
IEC 60099-8:2017 covers metal-oxide surge arresters with external series gap (externally gapped line arresters (EGLA)) that are applied on overhead transmission and distribution lines, only to protect insulator assemblies from lightning-caused flashovers. This document defines surge arresters to protect the insulator assembly from lightning-caused over-voltages only. Therefore, and since metal-oxide resistors are not permanently connected to the line, the following items are not considered for this document: - switching impulse spark-over voltage; - residual voltage at steep current and switching current impulse; - thermal stability; - long-duration current impulse withstand duty; - power-frequency voltage versus time characteristics of an arrester; - disconnector test; - aging duties by power-frequency voltage. Considering the particular design concept and the special application on overhead transmission and distribution lines, some unique requirements and tests are introduced, such as the verification test for coordination between insulator withstand and EGLA protective level, the follow current interrupting test, mechanical load tests, etc. Designs with the EGLA's external series gap installed in parallel to an insulator are not covered by this document. This second edition cancels and replaces the first edition published in 2011. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition: The Lightning discharge capability test has been completely re-written and re-named to Test to verify the repetitive charge transfer rating, Qrs with lightning discharges to reflect changes introduced in IEC 60099-4 Ed.3 (2014) regarding new methods for rating the energy and charge handling capability of metal-oxide arresters. In addition to testing to evaluate the performance of the MO resistors, procedures for evaluating the performance of the EGLA series gaps have been introduced. - Omissions from Ed. 1 of this standard have been included, notably an RIV test and a means for determining the thermal time constant of the SUV portion of the EGLA. - Definitions for new terms have been added - A number of NOTES in Ed. 1 have been converted to normative requirements Keywords: externally gapped line arresters (EGLA), lightning-caused over-voltages
Abstract
Overview
IEC 60099-8:2017 is the International Electrotechnical Commission standard for metal-oxide surge arresters with external series gap (externally gapped line arresters, EGLA) used on overhead transmission and distribution lines of a.c. systems above 1 kV. The standard is limited to EGLAs applied solely to protect insulator assemblies from lightning-caused over-voltages (lightning-caused flashovers). Edition 2.0 (2017) is a technical revision that aligns rating and test methods with IEC 60099-4 Ed.3 (2014) and introduces updated tests and normative requirements.
Key topics and requirements
- Scope and exclusions: Covers EGLAs where metal-oxide resistors are not permanently connected to the line. It explicitly excludes several items from consideration, such as switching-impulse spark‑over voltage, residual voltage at steep-front and switching impulses, thermal stability, long-duration current impulse duty, power-frequency voltage vs. time characteristics, disconnector testing, and aging duties by power‑frequency voltage.
- Identification & classification: Standard ratings (voltages, frequencies, nominal discharge currents) and service-condition definitions for overhead line applications.
- Type, routine and acceptance tests: Detailed procedures for insulation withstand, residual-voltage, high-current duty, lightning discharge capability and new repetitive charge transfer rating (Qrs) tests, short‑circuit performance, mechanical load and vibration tests, weather‑ageing, and radio‑interference voltage (RIV) testing.
- Series-gap specific tests: New procedures for evaluating the performance and repetitive charge/energy handling of the EGLA series gap in addition to MO resistor testing.
- Protection coordination & follow current interrupting: Tests to verify coordination between insulator withstand and EGLA protective level and to confirm follow‑current interrupting capability under realistic conditions.
- Mechanical and environmental requirements: Bending, vibration, wind‑load and mounting considerations plus guidance for special service conditions and end‑of‑life criteria.
Practical applications
- Selection, specification and type‑approval of EGLAs for overhead transmission and distribution lines to reduce lightning‑caused flashovers.
- Test programs and acceptance criteria used by manufacturers and test laboratories to validate EGLA designs.
- Utility procurement and installation specifications to ensure EGLAs meet coordination, mechanical and environmental performance for power systems above 1 kV.
Who should use this standard
- Transmission and distribution utilities specifying line protection against lightning-caused over-voltages
- Surge‑arrester manufacturers and design engineers developing EGLA products
- Independent test laboratories conducting type, routine and acceptance tests
- Standards and compliance engineers preparing product documentation and procurement specs
Related standards
- IEC 60099‑4 (metal-oxide surge arresters - energy/charge rating methods) - referenced for Qrs methods
- Other parts of the IEC 60099 series for general surge arrester design and testing
Keywords: externally gapped line arresters (EGLA), lightning‑caused over‑voltages, surge arresters, metal‑oxide arresters, repetitive charge transfer rating (Qrs).
Технические детали
- Технический комитет
- TC 37 - Surge arresters
- SKU
- IEC 60099-8:2017
Похожие стандарты
Стандарты, упомянутые в описании
IEC TR 60099-10:2024
ДействующийSurge arresters - Part 10: Rationale for tests specified by IEC 60099-4:2014
Overview IEC TR 60099-10:2024 is a Technical Report from the IEC that explains the rationale behind the tests specified in IEC 60099-4:2014 for surge arresters. It is applicable to all test types and…
IEC 60099-4:2014
ДействующийSurge arresters - Part 4: Metal-oxide surge arresters without gaps for a.c. systems
Overview IEC 60099-4:2014, developed by the International Electrotechnical Commission (IEC), specifies requirements and testing procedures for metal-oxide surge arresters without gaps, intended for l…
IEC 60099-6:2019
ДействующийSurge arresters - Part 6: Surge arresters containing both series and parallel gapped structures - System volt…
Overview IEC 60099-6:2019 is an international standard developed by the International Electrotechnical Commission (IEC) that specifies requirements and testing procedures for metal-oxide surge arrest…