ISO 1452-2:2009
Plastics piping systems for water supply and for buried and above-ground drainage and sewerage under pressure — Unplasticized poly(vinyl chloride) (PVC-U) — Part 2: Pipes
Plastics piping systems for water supply and for buried and above-ground drainage and sewerage under pressure — Unplasticized poly(vinyl chloride) (PVC-U) — Part 2: Pipes
- Статус документа:
- Действующий
- Формат:
- Электронный (PDF)
- Количество страниц:
- 23
- Дата публикации:
- 1 декабря 2009 г.
- Издание:
- ISO IS 1452 edition 1 version 1
- ICS:
- 23.040.20
ISO 1452-2:2009 specifies the characteristics of solid-wall pipes made from unplasticized poly(vinyl chloride) (PVC‑U) for piping systems intended for water supply and for buried and above ground drainage and sewerage under pressure. It also specifies the test parameters for the test methods referred to. In conjunction with ISO 1452-1 and ISO 1452-5, it is applicable to extruded PVC‑U pipes without a socket and pipes with a socket (integral or not), intended to be used for the following: - water mains and services buried in the ground; - conveyance of water above ground for both outside and inside buildings; - buried and above ground drainage and sewerage under pressure. It is applicable to piping systems intended for the supply of water under pressure up to and including 25 °C (cold water) intended for human consumption and for general purposes as well as for waste water under pressure. It is also applicable to pipes for the conveyance of water and waste water up to and including 45 °C and to a range of pipe sizes and pressure classes. It gives requirements concerning colours.
Abstract
Overview
ISO 1452-2:2009 - Plastics piping systems for water supply and for buried and above-ground drainage and sewerage under pressure - Unplasticized poly(vinyl chloride) (PVC‑U) - Part 2: Pipes - specifies the characteristics and test parameters for solid‑wall PVC‑U pipes used in pressured water and sewage systems. It applies to extruded pipes with or without sockets (integral or separate) intended for buried and above‑ground use, including potable water, services, mains and pressure drainage/sewerage.
Key topics and technical requirements
- Material requirements
- Pipe material conforms with ISO 1452‑1.
- Density at 23 °C: 1 350–1 460 kg/m³ (measured to ISO 1183‑1).
- Minimum Required Strength (MRS): ≥ 25 MPa, verified per ISO 1452‑1 procedures.
- Temperature and pressure range
- Designed for potable water under pressure up to and including 25 °C.
- Applicable for water and wastewater up to and including 45 °C (with selection guidance for 25–45 °C).
- Covers a range of pipe sizes and pressure classes; Annex A provides allowable operating pressures.
- Geometrical and dimensional controls
- Nominal outside diameters, mean diameters, wall thicknesses, tolerances and out‑of‑roundness measured per ISO 3126 and specified tolerances (see standard tables).
- Requirements for pipe lengths, socket dimensions, and pipe ends for ring‑seal or solvent‑cement joints.
- Mechanical and physical tests
- Appearance and colour
- Surface quality criteria; color rules: grey/blue/cream for water supply; grey/brown for drainage/sewerage (uniform through the wall).
- Ancillary requirements
- Sealing rings, adhesives, performance requirements and marking/identification are specified.
Applications and users
- Practical uses:
- Buried water mains and service pipes
- Above‑ground conveyance inside/outside buildings
- Pressure drainage and sewerage lines
- Who uses the standard:
- PVC‑U pipe manufacturers, product designers and compounders
- Water utilities, consulting engineers and specifiers
- Installers, plumbing contractors and procurement teams
- Test laboratories and conformity assessment bodies
Related standards
- ISO 1452 series: Part 1 (General), Part 3 (Fittings), Part 4 (Valves), Part 5 (Fitness for purpose)
- Test and properties standards: ISO 1167, ISO 3126, ISO 1183‑1, ISO 6259‑2, ISO 7686
- Joint/seal standards: EN 681‑1, adhesive test methods (ISO 7387‑1, ISO 9311‑1)
Keywords: ISO 1452-2:2009, PVC‑U pipes, plastics piping systems, water supply, drainage and sewerage under pressure, pipe dimensions, pressure classes, MRS, density, test methods.
Технические детали
- Технический комитет
- ISO/TC 138/SC 2 - Plastics pipes and fittings for water supplies
- SKU
- ISO 1452-2:2009
Похожие стандарты
Стандарты, упомянутые в описании
BS EN ISO 1452-1:2009
ДействующийPlastics piping systems for water supply and for buried and above-ground drainage and sewerage under pressure…
ISO 1183-1:2012
ОтменёнPlastics — Methods for determining the density of non-cellular plastics — Part 1: Immersion method, liquid py…
BS EN ISO 3126:2005
ДействующийPlastics piping systems. Plastics components. Determination of dimensions.
BS EN ISO 11670:2003
ДействующийLasers and laser-related equipment. Test methods for laser beam parameters. Beam positional stability.
ISO 6259-1:2015
ДействующийThermoplastics pipes — Determination of tensile properties — Part 1: General test method
Overview ISO 6259-1:2015 - Thermoplastics pipes: Determination of tensile properties - Part 1: General test method defines a short-term tensile test procedure for thermoplastic pipes. The standard sp…
ISO 2505:1981
ОтменёнUnplasticized polyvinyl chloride (PVC) pipes — Longitudinal reversion — Test methods and specification
ISO 7686:2005
ДействующийPlastics pipes and fittings — Determination of opacity
Overview ISO 7686:2005 specifies a test method for the determination of the opacity of plastics pipes and fittings. The standard defines how to measure the percentage of visible light (540–560 nm) th…
ISO 1452-4:2009
ДействующийPlastics piping systems for water supply and for buried and above-ground drainage and sewerage under pressure…
Overview ISO 1452-4:2009 defines requirements for PVC‑U (unplasticized polyvinyl chloride) valves used in plastics piping systems for water supply and for buried and above‑ground drainage and sewerag…