ISO 29463-5:2022
High-efficiency filters and filter media for removing particles in air — Part 5: Test method for filter elements
High-efficiency filters and filter media for removing particles in air — Part 5: Test method for filter elements
- Статус документа:
- Действующий
- Формат:
- Электронный (PDF)
- Количество страниц:
- 28
- Дата публикации:
- 31 марта 2022 г.
- Издание:
- ISO IS 29463 edition 2 version 1
- ICS:
- 91.140.30
This document specifies the test methods for determining the efficiency of filters at their most penetrating particle size (MPPS). It also gives guidelines for the testing and classification for filters with an MPPS of less than 0,1 μm (Annex B) and filters using media with (charged) synthetic fibres (Annex C). It is intended for use in conjunction with ISO 29463‑1, ISO 29463‑2, ISO 29463‑3 and ISO 29463‑4.
Abstract
Overview
ISO 29463-5:2022 - "High-efficiency filters and filter media for removing particles in air - Part 5: Test method for filter elements" - defines standardized test methods to determine filter element efficiency at the most penetrating particle size (MPPS). It is part of the ISO 29463 series (derived from EN 1822) and is intended to be used alongside ISO 29463‑1, ‑2, ‑3 and ‑4. The standard covers test apparatus, aerosol generation, particle-counting methods, test procedures, evaluation and reporting for HEPA/ULPA and related high‑efficiency filters.
Key topics and requirements
- MPPS-based efficiency testing: Efficiency is assessed at the MPPS (the particle size where penetration is highest); for many micro‑glass media MPPS is typically 0.12–0.25 μm. Annex B provides guidance for filters with MPPS ≤ 0.1 μm (e.g., membrane media).
- Test methods: Supports testing with mono‑disperse and poly‑disperse aerosols; allows particle counting with instruments such as OPC, CPC, or particle sizing systems (e.g., DMPS) where appropriate.
- Test rig and sampling: Defines test duct layout, air conditioning, aerosol mixing, filter mounting, pressure‑drop measurement and sampling locations to ensure representative upstream/downstream particle counts.
- Alternate and statistical methods: Includes alternate scan or statistical methods for specific filter groups (e.g., alternate method for groups H and U; statistical method for group E low‑efficiency filters).
- Charged fibre media: Annex C provides normative procedures and classification guidance for filters using media with (charged) synthetic fibres.
- Test documentation and maintenance: Specifies required test report content and maintenance/inspection of test apparatus to ensure repeatability and traceability.
Applications and users
ISO 29463-5 is used by:
- Filter manufacturers for product qualification and classification (HEPA/ULPA performance).
- Independent test laboratories performing standardized efficiency and leakage testing.
- HVAC and cleanroom engineers specifying filters for controlled environments (pharma, semiconductor, healthcare).
- Facility managers and procurement teams requiring verifiable filter performance data.
- Regulators and conformity assessors referencing standardized test results for compliance.
Practical benefits include reproducible, particle‑count‑based efficiency data at the MPPS, improved comparability between products, and methods tailored for advanced media (membranes, charged fibres).
Related standards
- ISO 29463‑1, ‑2, ‑3, ‑4 (series)
- ISO 21501‑4 (particle counting - OPC)
- ISO 5167‑1 (flow measurement)
- ISO 16890‑4 (conditioning for fractional efficiency)
Keywords: ISO 29463-5, HEPA testing, ULPA, MPPS, filter efficiency test, aerosol generation, particle counting, charged fibres, filter media.
Технические детали
- Технический комитет
- ISO/TC 142 - Cleaning equipment for air and other gases
- SKU
- ISO 29463-5:2022
Похожие стандарты
Стандарты, упомянутые в описании
ISO 29463-5:2011
ОтменёнHigh-efficiency filters and filter media for removing particles in air — Part 5: Test method for filter eleme…
BS EN 1822-1:2019
ДействующийHigh efficiency air filters (EPA, HEPA and ULPA). Classification, performance testing, marking.
BS ISO 29463-1:2024
ДействующийHigh efficiency filters and filter media for removing particles in air. Classification, performance, testing…
ISO 21501-4:2018
ДействующийDetermination of particle size distribution — Single particle light interaction methods — Part 4: Light scatt…
Overview ISO 21501-4:2018 specifies calibration and verification methods for light scattering airborne particle counters (LSAPC) used in clean spaces. The standard covers single-particle light intera…
ISO 5167-1:2003
ОтменёнMeasurement of fluid flow by means of pressure differential devices inserted in circular cross-section condui…
ISO 16890-4:2022
ДействующийAir filters for general ventilation — Part 4: Conditioning method to determine the minimum fractional test ef…
Overview ISO 16890-4:2022 - "Air filters for general ventilation - Part 4: Conditioning method to determine the minimum fractional test efficiency" defines a laboratory conditioning procedure used to…